Industrial UPS (DC Bus) 

Place of Origin: Zhejiang, China (Mainland) 
inquire
Add to My Favorites
HiSupplier Escrow
Share |

Product Detail

Model No.: DTS9310 6-80KVA

Key Features<br

Key Features
1. Full digital control technique
2. Intelligent detecting and monitoring function
3. Digital control static switch and zero changeover time
4. Full isolation between input and output
5. DC panel and utility power are full isolated.
6. Uses electric power standard cabinet.
7. It’s provided with over voltage protection, under voltage protection, over current protection, short circuit protection and some other protection functions.
8. Large LCD can display the input voltage, output voltage, current, frequency, battery voltage, charge-discharge current value, fault and other running conditions in Chinese and English.
9. At most 256 pieces of historic records can be showed. This makes it easier for users to analyze the power supply condition.
10.The static state bypass has strong anti-overload capacity.
Applications
Chemical factories, Power generating plants, Power distribution stations, electrical substations, electric power communication systems, and many other fields.

Technical Specifications of Industrial UPS DTS9310 Series

bigPhoto
 Mr. Misen

Tel: 86-755-81495850
Contact to this supplier

Related Search

Find more related products in following catalogs on Hisupplier.com

Company Info

Shenzhen SORO Electronics Company Group [China (Mainland)]


Business Type:Manufacturer
City: Shenzhen
Province/State: Guangdong
Country/Region: China (Mainland)

You May Like:

Product (193)

Model

DTS9310  6-80KVA

6KVA

10KVA

15KVA

20KVA

30KVA

40KVA

50KVA

60KVA

80KVA

Rated Capacity    

6KVA/

4.8KW

10KVA/

8KW

15KVA/

12KW

20KVA/

16KW

30KVA/

24KW

40KVA/

32KW

50KVA/

40KW

60KVA/

48KW

80KVA/

64KW

Rated Voltage

220V Single Phase (6-20KVA)/380VA

Rated Frequency

50/60HZ

AC Input

Voltage range

±20%

Frequency range

50/60HZ±10%

Soft start

0-100%   5sec

Power factor

0.95 (with input filter)

Bypass input

Voltage range

15%

Frequency range

50/60HZ±5%

 

 

Output

Voltage accuracy

220V±1% (Steady state load)  220V±3% (load fluctuation)

Frequency accuracy

50/60Hz±0.05Hz (Battery supply power)

Power factor

0.8

Harmonic distortion

Linear load<2%; non-linear<4%